1. Features
① Vertical core, flexible installation, can be fixed on the busbar or on the bottom plate;
② Suitable for protective occasions.
2. Ambient Conditions
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar
(about 650~800mmHg).
3. Operating Frequency Range: 20Hz~ 20k Hz
4. Insulation Thermal Class: Class B (130°C).
5. Safety Features:
① Insulation resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 6KV 50Hz/1min.
③ Fire retardancy: In conformity with UL94-V0.
6. Outline Drawing, Installation Dimension
and Coil Diagram: ( tolerance ± 0.5 mm)
① Outline drawing and installation dimensions
are shown in Figure 1:
② The coil diagram is shown in Figure 2:
7. Typical Application and Performance Parameters:
See the table below for performance parameters when applied as shown in Figure 3 .
Model | Parameter | Rated Input Current | Rated Output Voltage | Non-linearity | Specified Load | Overload Capacity |
TAR3659-1 | 1A:3mV | 40A | 0.12V | 0.5% | 12kΩ | 10 times |
Note: This series of transformers is used in systems protected by explosion-proof systems。
● Notes:
a. In practical application, the sampling resistance should be equal to the rated value given in the above table;
b. If the conversion ratio required by the user is different from the above, it can be customized according to the user's requirements.