1.Features:
① The printed circuit board is directly welded and installed, and the appearance is beautiful;
② Small size, high precision; fully enclosed, good mechanical and environmental resistance, strong voltage isolation capability, safe and reliable.
2.Ambient conditions:
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg).
 
3.Operating Frequency Range: 2kHz~100k Hz
4.Insulation Thermal Class: Class B (130 ℃)
5.Safety Features:
① Insulation resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 2.5KV 50Hz/1min;
③ Fire retardancy: In conformity with UL94-V0. 
6.Outline Drawing, Installation Dimension and Coil Diagram : ( tolerance±0.3 mm)
① Outline drawing and installation dimensions are shown in Figure 1:
② The coil diagram is shown in Figure 2:

   
 

7.Typical Application and Technical Parameters:( tolerance±0.3mm )
When the sampling voltage is directly obtained by the resistance method (as shown in Figure 3 ) , the performance parameters are shown in the table below .
Model  | Rated Input Current  | Rated Output Current  | Rated Sampling Resistance RL  | Rated Sampling Voltage  | Non-linearity  | Linear Range  | 
TA0916-01  | 2A  | 4mA  | 1000Ω  | 4V  | ≤2%  | ≥1.5 times of the rated value  | 
TA0916-02  | 2A  | 2mA  | 4000Ω  | 8V  | ≤1.5%  | ≥2 times of the rated value  | 
8.Attention:
① Connect the primary winding of the current transformer in series with the measured current loop. Operate the secondary winding in a near short-circuit mode.
② Do not allow the secondary winding of the current transformer to be open-circuited. Do not install any fuse on the secondary winding.