1.Features:
① Vertical core, flexible installation, can be fixed on the busbar or on the bottom plate;
② It can be equipped with various types of busbars, such as flat busbars, round busbars or cables;
③ The output terminal is a screw fastened crimping type standard terminal, which is convenient for wiring at the engineering site;
④ Box structure, closed plastic case, beautiful appearance.
2.Ambient Conditions:
① Ambient temperature: -30℃~+70℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg).
3.Operating Frequency Range: 50 Hz or 60 Hz
4.Insulation Thermal Class:Class E ( 120℃)
5.Safety Features:
① Insulation resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 3000V 50Hz/1min;
③ Fire retardancy: In conformity with UL94-V0.
6. Outline Drawing, Installation Dimension and Coil Diagram: (tolerance±1mm)
① Outline drawing and installation dimensions are shown in Figure 1:
② The coil diagram is shown in Figure 2:
● Note: Each product is supplied with two bottom plate feet, one busbar foot, two screws and suction cups for fixing the busbar, and the installation instructions are as follows.
③ Installation Notes:
● When fixing to the base plate:
Take two bottom plate feet ( supplied with the product ) Insert it into the foot socket on the bottom plate of the transformer as shown in Figure 3. The center distance of the mounting holes is 60 × 71; the mounting hole diameter of the feet is Φ5.0; the transformer can be fixed on the bottom plate with M5 screws.
● When fixing to the busbar:
Take a busbar support foot with M5 holes ( supplied with the product ) and insert it into the busbar support foot slot in the middle of the transformer as shown in Figure 3. The center distance of the M5 holes is 59 , and the transformer can be fixed on the busbar with M5 screws.
7. Typical Application and Performance Parameters:
See the table below for performance parameters when applied as shown in Figure 4:
Model | Rated Input Current | Rated Output Current | Rated Sampling Resistance RL | Rated Sampling Voltage | Non-linearity |
TAM10162-1 | 250A | 5A | 0.166Ω | 0.83V | ≤0.5% |
TAM10162-2 | 300A | 5A | 0.2Ω | 1V | ≤0.5% |
TAM10162-3 | 400A | 5A | 0.266Ω | 1.33V | ≤0.5% |
TAM10162-4 | 500A | 5A | 0.333Ω | 1.66V | ≤0.5% |
TAM10162-5 | 600A | 5A | 0.4Ω | 2V | ≤0.5% |
TAM10162-6 | 750A | 5A | 0.5Ω | 2.5V | ≤0.5% |
TAM10162-7 | 800A | 5A | 0.533Ω | 2.66V | ≤0.5% |
TAM10162-8 | 1000A | 5A | 0.666Ω | 3.33V | ≤0.5% |
TAM10162-9 | 1200A | 5A | 0.8Ω | 4V | ≤0.5% |
TAM10162-10 | 1250A | 5A | 0.833Ω | 4.16V | ≤0.5% |
TAM10162-11 | 1500A | 5A | 1Ω | 5V | ≤0.5% |
TAM10162-12 | 2000A | 5A | 1.33Ω | 6.66V | ≤0.5% |
TAM10162-13 | 2500A | 5A | 1.66Ω | 8.33V | ≤0.5% |
TAM10162-14 | 3000A | 5A | 2Ω | 10V | ≤0.5% |
● Notes:
a. In practical applications, the sampling resistance should be less than or equal to the rated value given in the above table, which will improve the nonlinearity and phase shift;
b. If the conversion ratio required by the user is different from the above, it can be customized according to the user's requirements.
8.Attention:
① Connect the primary of the current transformer in series with the measured current loop, and operate the secondary in near short circuit mode.
② Do not allow the secondary of the current transformer to be open circuit and do not install any fuse.