TAM10162 Series Vertical Core Box-type AC Current Transformer
83.png
TAM10162 Series Vertical Core Box-type AC Current Transformer
Features:
① Vertical core, flexible installation, can be fixed on the busbar or on the bottom plate;
② It can be equipped with various types of busbars, such as flat busbars, round busbars or cables;
③ The output terminal is a screw fastened crimping type standard terminal, which is convenient for wiring at the engineering site;
④ Box structure, closed plastic case, beautiful appearance.
TAM10162 General Technical Specifications for Standard Products:

1Features: 

 Vertical core, flexible installation, can be fixed on the busbar or on the bottom plate;

 It can be equipped with various types of busbars, such as flat busbars, round busbars or cables;

 The output terminal is a screw fastened crimping type standard terminal, which is convenient for wiring at the engineering site;

 Box structure, closed plastic case, beautiful appearance.

 

2Ambient Conditions:

① Ambient temperature:  -30℃~+70℃;

② Relative humidity: ≤90% at 40℃;

③ Atmospheric pressure: 8601060mbar(about 650800mmHg).

 

3Operating Frequency Range: 50 Hz or 60 Hz

 

4Insulation Thermal ClassClass E ( 120℃)

 

5Safety Features:

① Insulation resistance: >1000MΩ in normal condition;

② Insulation withstand voltages: 3000V 50Hz/1min;

③ Fire retardancy: In conformity with UL94-V0.

 

6. Outline Drawing, Installation Dimension and Coil Diagram: (tolerance±1mm)

① Outline drawing and installation dimensions are shown in Figure 1:

 The coil diagram is shown in Figure 2:

image.png

image.png

Note: Each product is supplied with two bottom plate feet, one busbar foot, two screws and suction cups for fixing the busbar, and the installation instructions are as follows.







③ Installation Notes:

● When fixing to the base plate:


Take two bottom plate feet ( supplied with the product ) Insert it into the foot socket on the bottom plate of the transformer as shown in Figure 3. The center distance of the mounting holes is 60 × 71; the mounting hole diameter of the feet is Φ5.0; the transformer can be fixed on the bottom plate with M5 screws.

● When fixing to the busbar:

Take a busbar support foot with M5 holes ( supplied with the product ) and insert it into the busbar support foot slot in the middle of the transformer as shown in Figure 3. The center distance of the M5 holes is 59 , and the transformer can be fixed on the busbar with M5 screws.

image.png

7. Typical Application and Performance Parameters:

See the table below for performance parameters when applied as shown in Figure 4:

Model

Rated Input Current

Rated Output Current

Rated Sampling Resistance RL

Rated Sampling Voltage

Non-linearity

TAM10162-1

250A

5A

0.166Ω

0.83V

≤0.5%

TAM10162-2

300A

5A

0.2Ω

1V

≤0.5%

TAM10162-3

400A

5A

0.266Ω

1.33V

≤0.5%

TAM10162-4

500A

5A

0.333Ω

1.66V

≤0.5%

TAM10162-5

600A

5A

0.4Ω

2V

≤0.5%

TAM10162-6

750A

5A

0.5Ω

2.5V

≤0.5%

TAM10162-7

800A

5A

0.533Ω

2.66V

≤0.5%

TAM10162-8

1000A

5A

0.666Ω

3.33V

≤0.5%

TAM10162-9

1200A

5A

0.8Ω

4V

≤0.5%

TAM10162-10

1250A

5A

0.833Ω

4.16V

≤0.5%

TAM10162-11

1500A

5A

5V

≤0.5%

TAM10162-12

2000A

5A

1.33Ω

6.66V

≤0.5%

TAM10162-13

2500A

5A

1.66Ω

8.33V

≤0.5%

TAM10162-14

3000A

5A

10V

≤0.5%

Notes:

a. In practical applications, the sampling resistance should be less than or equal to the rated value given in the above table, which will improve the nonlinearity and phase shift;

b. If the conversion ratio required by the user is different from the above, it can be customized according to the user's requirements.

8Attention:

 Connect the primary of the current transformer in series with the measured current loop, and operate the secondary in near short circuit mode.

 Do not allow the secondary of the current transformer to be open circuit and do not install any fuse.