1.Features:
① Vertical core, flexible installation, can be fixed on the busbar or on the bottom plate;
② It can be equipped with various types of busbars, such as flat busbars, round busbars or cables;
③ The output terminal is a screw fastened crimping type standard terminal, which is convenient for wiring at the engineering site;
④ Box structure, closed plastic case, beautiful appearance.
2.Ambient Conditions:
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg).
3.Operating Frequency Range: 20Hz~1kHz
4.Insulation Thermal Class:Class B (130℃)
5.Safety Features:
① Insulation resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 4000V 50Hz/1min;
③ Fire retardancy: In conformity with UL94-V0.
6.Outline Drawing, Installation Dimension and Coil Diagram: (tolerance±1mm)
① Outline drawing and installation dimensions are shown in Figure 1:
② The coil diagram is shown in Figure 2:
● Note: Each product is supplied with two bottom plate feet, one busbar foot and screws for fixing the busbar. See below for installation instructions.
③ Installation Notes:
● When fixing to the bottom plate: take two feet ( supplied with the product ) and insert them into the foot sockets on the bottom plate as shown in Figure 3. The center distance of the installation holes is 60 × 53 ; the diameter of the mounting holes of the feet is Φ 5 ; the transformer can be fixed on the bottom plate with M5 screws; (note: there are also 6 8 hole distance mounting plates optional)
● When fixing to the busbar: take a foot with M5 holes ( supplied with the product ) and insert it into the busbar foot slot as shown in Figure 3. The center distance of the M5 holes is 59 , and the transformer can be fixed on the busbar with M5 screws.
7. Typical Application and Performance Parameters:
See the table below for performance parameters when applied as shown in Figure 4
Model | Rated Input Current | Rated Output Current | Rated Sampling Resistance RL | Rated Sampling Voltage | Phase Shift | Non-linearity | Linear Range |
TAR 6589-1 | 2500A | 1A | 2Ω | 2V | ≤30' | ≤0.5% | 2 times rated |
TAR 6589-2 | 2000A | 1A | 2Ω | 2V | ≤30' |
● Notes:
a. In practical applications, the sampling resistance should be less than or equal to the rated value given in the above table, which will improve the nonlinearity and phase shift;
b. If the conversion ratio required by the user is different from the above, it can be customized according to the user's requirements.
8. Attention:
① The primary of the current transformer should be connected in series with the current circuit under test, and the secondary should operate in approximate short-circuit mode.
② The secondary circuit of the current transformer must not be allowed to open circuit during operation, so please do not install any fuse.