1.Features:
① Directly fixed on the 1.7 × 21 flat busbar ;
② Fully enclosed, good mechanical and environmental resistance, strong voltage isolation capability, safe and reliable.
2.Ambient Conditions:
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg).
3.Operating Frequency Range: 20Hz~1kHz
4.Insulation Thermal Class:Class B grade ( 130 ℃ )
5.Safety Features:
① Insulation resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 6000V 50Hz/1 min;
③ Fire retardancy: In conformity with UL94-V0.
6. Outline Drawing, Installation Dimension and Coil Drawing :( tolerance ± 0.5mm )
7. Performance Parameters:
See the table below for the application performance parameters shown in Figure 3.
Model | Rated Input Current | Rated Output Current | Rated Sampling Resistance | Rated Sampling Voltage | Phase Shift | Non-linearity | Linear Range |
TA 2739-01 | 1 00A | 1 00mA | 20Ω | 2V | ≤30' | ≤0.5% | ≥3 times of the rated value |
TA 2739-02 | 1 00A | 50mA | 80Ω | 4V | ≤30' | ≤0.5% |
●Notes:
a. In practical applications, the sampling resistance should be less than or equal to the rated value given in the above table, which will improve the nonlinearity and phase shift;
b. If the conversion ratio required by the user is different from the above, it can be customized according to the user's requirements.
8.Attention:
① Connect the primary winding of the current transformer in series with the measured current loop, and operate the secondary winding in near short-circuit mode.
② Do not allow the secondary winding of the current transformer to be open-circuited and do not install any fuse in the secondary circuit.