1.Features:
① The output coil comes with standard plug-in leads for easy use and an elegant appearance.
② It is completely sealed, with strong mechanical and environmental endurance, high dielectric strength, ensuring safety and reliability.
2.Ambient Conditions:
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg);
3.Operating Frequency Range: 20Hz~1kHz
4.Insulation Thermal Class:Class F (155℃)
5.Safety Features:
① Insulation resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 6000V 50Hz/1min;
③ Fire retardancy: In conformity with UL94-V0.
6.Outline Drawing, Installation Dimension and Coil Diagram:( tolerance ± 0.5mm )
7.Typical Application and Parameters:
The parameters in this application as shown in the figure are listed in Table below:
Table:
Model | Rated Input Current | Rated Output Current | Rated Sampling Resistance RL | Rated Sampling Voltage | Phase Shift | Non Linearity | Linear Range | Withstand Voltage |
TA2030-00 | 120A | 40mA | 150Ω | 6V | ≤6’ | ≤0.2% | ≥1.5 times of rated value | ≥6KV |
TA2030-00M | 120A | 40mA | 187.5Ω | 7.5V | ≤7.5’ | ≤0.25% | ||
TA2030-01 | 100A | 50mA | 80Ω | 4V | ≤8’ | ≤0.2% | ||
TA2030-01M | 100A | 50mA | 100Ω | 5V | ≤10’ | ≤0.25% | ||
TA2030-02 | 90A | 60mA | 50Ω | 3V | ≤10’ | ≤0.2% | ||
TA2030-02M | 90A | 60mA | 62.5Ω | 3.75V | ≤12.5’ | ≤0.25% | ||
TA2030-03 | 60A | 60mA | 30Ω | 1.8V | ≤10’ | ≤0.2% | ||
TA2030-03M | 60A | 60mA | 37.5Ω | 2.25V | ≤12.5’ | ≤0.25% |
● Notes:
a.In practical applications, the sampling resistor should be smaller than or equal to the rated value given in table above in order to improve the non-linearity and phase shift.
b.We can have it customer-made if required current ratio is not listed in the table above.
8.Attention:
① Connect the primary winding of the current transformer in series with the measured current loop, and operate the secondary winding in near short-circuit mode.
② Do not allow the secondary winding of the current transformer to be open-circuited and do not install any fuse in the secondary circuit.