1.Features:
① The primary coil is built-in inside; being able to be directly soldered on PCB.
② Completely sealed, strong mechanical and environmental endurance, strong dielectric strength, and elegant outline.
2.Ambient Conditions:
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg).
3.Operating Frequency Range: 20Hz~1kHz
4.Insulation Thermal Class:Class F (155℃)
5.Safety Features:
① Insulation resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 2000V 50Hz/1min in line-frequency;
③ Fire retardancy: In conformity with UL94-V0.
6.Outline Drawing, Installation Dimension and Coil Diagram:( tolerance ± 0.5mm )
7.Typical Application and Technical Parameters:
①The parameters are listed in Table 1 while the sampling voltage is obtained directly by using a resistor (as shown in Fig.1 below).
②The parameters are listed in Table 2 while the sampling voltage is obtained by using an IC (as shown in Fig.2 below).
Table 1:
Model | Rated Input Current | Rated Output Current | Rated Sampling Resistance RL | Rated Sampling Voltage | Phase Shift | Non Linearity | Linear Range | Withstand Voltage |
TA1906-01 | 2.5A | 2.5mA | 200Ω | 0.5V | ≤60’ | ≤0.5% | ≥2 times of the rated value | ≥2KV |
TA1906-02 | 2.5A | 1.25mA | 800Ω | 1.0V | ≤60’ | |||
TA1906-03 | 5A | 1.67mA | 900Ω | 1.5V | ≤50’ | |||
TA1906-04 | 5A | 1.25mA | 1600Ω | 2.0V | ≤50’ |
Table2:
Model | Rated Input Current | Rated Output Current | Rated Sampling Voltage | Phase Shift | Non Linearity | Linear Range | Withstand Voltage |
TA1906-01 | 2.5A | 2.5mA | ≤1/2times of IC power supply | ≤30’ | ≤0.3% | ≥2 times of the rated value | ≥2KV |
TA1906-02 | 2.5A | 1.25mA | |||||
TA1906-03 | 5A | 1.67mA | |||||
TA1906-04 | 5A | 1.25mA |
8.Attention:
① Connect the primary winding of the current transformer in series with the measured current loop, and operate the secondary winding in near short-circuit mode.
② Do not allow the secondary winding of the current transformer to be open-circuited and do not install any fuse in the secondary circuit.