1.Features:
① Vertical core-through, printed circuit board directly soldered and installed ;
② Small size, high precision , beautiful appearance;
③ Fully enclosed, good mechanical and environmental resistance, strong voltage isolation capability.
2.Ambient conditions:
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg).
3.Operating Frequency Range: 20Hz~1kHz
4.Insulation Thermal Class:Class B (130°C)
5.Safety Features:
① Insulation resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 6000V 50Hz/1min;
③ Fire retardancy: In conformity with UL94-V0.
6. Outline Drawing, Installation Dimension and Coil diagram : ( tolerance ± 0.5mm )
7. Typical Application and Performance Parameters:
① When the sampling voltage is directly obtained by the resistance method ( as shown in Figure 3 ) , the performance parameters are shown in Table 1;
② When using the IC method to obtain the sampling voltage ( as shown in Figure 4 ) , the performance parameters are shown in Table 2.
Table 1 :
Model | Rated Input Current | Rated Output Current | Rated Sampling Resistance | Rated Sampling Voltage | Phase Shift | Non-linearity | Linear Range |
TA1319-01 | 5A | 5 mA | 140Ω | 0.7V | ≤ 30' | ≤0. 2 % | ≥ 2 times of the rated value |
TA1319-01M | 5A | 5 mA | 200Ω | 1.0V | ≤ 30' | ≤0. 25 % | |
TA1319-02 | 5A | 2.5 mA | 560Ω | 1.4V | ≤ 25' | ≤0. 2 % | |
TA1319-02M | 5A | 2.5 mA | 800Ω | 2.0V | ≤ 25' | ≤0. 25 % |
Table 2:
Model | Rated Input Current | Rated Output Current | Rated Sampling Voltage | Phase Shift | Non-linearity | Linear Range |
TA1319-1 | 5A | 5 mA | ≤1/2 times IC power supply voltage | ≤5' | ≤0.1% | ≥ 2 times of the rated value |
TA1319-1M | 5A | 5 mA | ||||
TA1319-2 | 5A | 2.5 mA | ||||
TA1319-2M | 5A | 2.5 mA |
8.Attention:
① Connect the primary winding of the current transformer in series with the measured current loop, and operate the secondary winding in near short-circuit mode.
② Do not allow the secondary winding of the current transformer to be open-circuited and do not install any fuse in the secondary circuit.