1.Features:
① The busbar is built-in and directly soldered to the printed circuit board for installation;
② Compact in size, high precision, and aesthetic appearance;
③ Fully enclosed, with good mechanical and environmental performance, and strong voltage isolation capability.
2.Ambient Conditions:
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg);
3.Operating Frequency Range: 20Hz~1kHz
4.Insulation Thermal Class:Class F (155℃).
5.Safety features:
① Insulation resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 6000V 50Hz/1min;
③ Fire retardancy: In conformity with UL94-V0.
6.Outline Drawing, Installation Dimension and Coil Diagram:
7.Typical Application and Technical Parameters:
①The parameters are listed in Table 1 while the sampling voltage is obtained directly by using a resistor (as shown in Fig.1 below).
② The parameters are listed in Table 2 while the sampling voltage is obtained by using an IC (as shown in Fig.2 below).
Table 1:
Model | Rated Input Current | Rated Output Current | Rated Sample Resistor RL | Rated Sample Voltage | Phase Shift | Non Linearity | Linear Range | Withstand Voltage |
TA1016-1 | 10A | 10mA | 50Ω | 0.5V | ≤20’ | ≤0.2% | ≥1.5 times of rated value | ≥6KV |
TA1016-1M | 10A | 10mA | 62.5Ω | 0.625V | ≤25’ | ≤0.25% | ||
TA1016-2 | 5A | 2.5mA | 400Ω | 1V | ≤20’ | ≤0.2% | ≥2 times of rated value | |
TA1016-2M | 5A | 2.5mA | 500Ω | 1.25V | ≤25’ | ≤0.25% |
Table 2:
Model | Rated Input Current | Rated Output Current | Rated Sample Voltage | Phase Shift | Non Linearity | Linear Range | Withstand Voltage |
TA1016-1 | 10A | 10mA | ≤1/2 IC’s power supply | ≤5’ | ≤0.1% | ≥2 times of rated value | ≥6KV |
TA1016-1M | 10A | 10mA | |||||
TA1016-2 | 5A | 2.5mA | |||||
TA1016-2M | 5A | 2.5mA |
8.Attention:
① Connect the primary winding of the current transformer in series with the measured current loop, and operate the secondary winding in near short-circuit mode.
② Do not allow the secondary winding of the current transformer to be open-circuited and do not install any fuse in the secondary circuit.