1.Features:
① The input coil is builtin, the printed circuit board is directly welded and installed, and the appearance is beautiful;
② Small size, high precision; fully enclosed, good mechanical and environmental resistance, strong voltage isolation capability, safe and reliable.
2.Ambient Conditions
① Ambient temperature: 55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg).
3.Operating Frequency Range: 20Hz~1kHz
4.Insulation Thermal Class:Class B (130°C)
5.Safety Features:
① Dielectric resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 2000V 50Hz/1min;
③ Fire retardancy: In conformity with UL94V0.
6. Outline Drawing, Installation Dimension and Coil Diagram : ( tolerance±0.5 mm)
7.Typical Application and Technical Parameters:
① When the sampling voltage is directly obtained by the resistance method (as shown in Figure 3), the performance parameters are shown in Table 1;
② When using the IC method to obtain the sampling voltage (as shown in Figure 4), the performance parameters are shown in Table 2.
Table 1:
Model | Rated Input Current | Rated Output Current | Rated Sampling Resistor | Rated Sampling Voltage | Phase Shift | Non- Linearity | Linear Range |
TA1013A - 1M | 5A | 2.5mA | 800Ω | 2V | ≤30' | ≤0.2% | ≥2 times of the rated value |
Table 2:
Model | Rated Input Current | Rated Output Current | Rated Sampling Voltage | Phase Shift | Non-linearity | Linear Range |
TA1013A- 1M | 5A | 2.5mA | ≤1/2 times IC power supply voltage | ≤5' | ≤0.1% | ≥2 times of the rated value |
8.Attention:
① Connect the primary winding of the current transformer in series with the measured current loop, and operate the secondary winding in near short-circuit mode.
② Do not allow the secondary winding of the current transformer to be open-circuited and do not install any fuse in the secondary circuit.