1.Features:
① This product has a compact size, elegant outline, and a built-in primary coil that can be directly welded on PCB for easy use.
② It is completely sealed for high precision, strong mechanical and environmental endurance, strong dielectric strength, and safe and reliable performance.
2.Ambient Conditions:
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg);
3.Operating Frequency Range: 20Hz~1kHz
4.Insulation Thermal Class:Class F (155℃)
5.Safety Features:
① Dielectric resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 2000V 50Hz/1 min;
③ Fire retardancy: In conformity with UL94-Vo.
6.Outline Drawing, Installation Dimension and Coil Diagram.( tolerance ± 0.5mm)
7.Typical usage and Technical Parameters:
①The parameters are listed in Table 1 while the sampling voltage is obtained directly by using a resistor (as shown in Fig.1 below).
②The parameters are listed in table 2 while the sampling voltage is obtained by using an IC (as shown in Fig.2 below).
Table 1:
Model | Rated Input Current | Rated Output Current | Rated Sampling Resistor RL | Rated Sampling Voltage | Phase Shift | Non Linearity | Linear Range | Withstand Voltage |
TA1013-1Z | 2A | 2mA | 200Ω | 0.4V | ≤30’ | ≤0.2% | ≥2 times of the rated value | ≥2KV |
TA1013-1ZM | 2A | 2mA | 250Ω | 0.5V | ≤40’ | ≤0.25% | ||
TA1013-2Z | 1.25A | 2.5mA | 300Ω | 0.75V | ≤20’ | ≤0.2% | ||
TA1013-2ZM | 1.25A | 2.5mA | 380Ω | 0.95V | ≤27’ | ≤0.25% | ||
TA1013-3Z | 500mA | 5mA | 100Ω | 0.5V | ≤15’ | ≤0.2% | ||
TA1013-3ZM | 500mA | 5mA | 125Ω | 0.625V | ≤19’ | ≤0.25% |
Table 2:
Model | Rated Input Current | Rated Output Current | Rated Sampling Voltage | Phase Shift | Non Linearity | Linear Range | Withstand Voltage |
TA1013-1Z | 2A | 2mA | ≤1/2times of IC power supply | ≤5’ | ≤0.1% | 2 times of the rated value | ≥2KV |
TA1013-1ZM | 2A | 2mA | |||||
TA1013-2Z | 1.25A | 2.5mA | |||||
TA1013-2ZM | 1.25A | 2.5mA | |||||
TA1013-3Z | 500mA | 5mA | |||||
TA1013-3ZM | 500mA | 5mA |
8.Attention:
① Connect the primary winding of the current transformer in series with the measured current loop, and operate the secondary winding in near short-circuit mode.
② Do not allow the secondary winding of the current transformer to be open-circuited and do not install any fuse in the secondary circuit.