1.Features:
① Can be directly welded onto PCB.
② Compact size, high precision, and elegant design.
③Fully encapsulated, with strong mechanical and environmental endurance, and excellent insulating capabilities.
2.Ambient Conditions
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg).
3.Operating Frequency Range: 20Hz~1kHz
4.Insulation Thermal Class:Class B (130℃).
5.Safety Features:
① Insulation resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 6KV 50Hz/1min;
③ Fire retardancy: In conformity with UL94-V0.
6.Outline Drawing, Installation Dimension, and Coil Diagram: ( tolerance ± 0.5mm)
7.Typical Application and Technical Parameters:
①The parameters are listed in Table 1 while the sampling voltage is obtained directly by using a resistor (as shown in Fig.1 below).
②The parameters are listed in Table 2 while the sampling voltage is obtained by using an IC (as shown in Fig.2 below)
Table 1:
Model | Rated Input Current | Rated Output Current | Rated Sampling Resistance | Rated Sampling Voltage | Phase Shift | Non-linearity | Linear Range | Withstand Voltage |
TA0913-1M | 5A | 5mA | 150Ω | 0.75V | ≤15’ | ≤0.2% | ≥1.5 times of the rated value | ≥6KV |
TA0913-2M | 5A | 2.5mA | 600Ω | 1.5V | ≤10’ |
Table 2:
Model | Rated Input Current | Rated Output Current | Rated Sampling Voltage | Phase Shift | Non-linearity | Linear Range | Withstand Voltage |
TA0913-1M | 5A | 5mA | ≤1/2 IC’s power supply | ≤5’ | ≤0.1% | ≥2 times of the rated value | ≥6KV |
TA0913-2M | 5A | 2.5mA |
8.Attention:
① Connect the primary winding of the current transformer in series with the measured current loop, and operate the secondary winding in near short-circuit mode.
② Do not allow the secondary winding of the current transformer to be open-circuited and do not install any fuse in the secondary circuit.