1.Features:
① The busbar is built-in, and the printed circuit board is directly welded and installed;
② Small size, compact structure, beautiful appearance;
③ Fully enclosed, good mechanical and environmental resistance, strong voltage isolation capability, and beautiful appearance .
2.Ambient Conditions:
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar
(about 650~800mmHg).
3.Operating Frequency Range: 20Hz~1kHz
4.Insulation Thermal Class: Class B (130°C)
5.Safety Features:
① Dielectric resistance: >1000MΩ in normal condition;
② Insulation withstand voltages: 2KV 50Hz/1min;
③ Fire retardancy: In conformity with UL94-V0.
6. Outline Drawing, Installation Dimension and Coil Diagram : ( tolerance ± 0.5mm)
7. Performance Parameters:
Model | Rated Input Current | Rated Output Current | Rated Sampling Resistance | Rated Sampling Voltage | Non-linearity | Phase Shift |
TA0814-01M | 10A | 10mA | 100Ω | 1V | ≤0.25% | ≤30' |
TA0814-02M | 10A | 5mA | 400Ω | 2V | ≤0.25% | ≤ 20' |
8.Attention:
① Connect the primary winding of the current transformer in series with the measured current loop, and operate the secondary winding in near short-circuit mode.
② Do not allow the secondary winding of the current transformer to be open-circuited and do not install any fuse in the secondary circuit.