TA8595 Series Zero Sequence Current Transformer
LI138V2 /2016
1.Features:
① It can measure the zero-sequence current in the system whose main circuit current is below 500A;
② 
Fully enclosed, good mechanical and environmental resistance, strong voltage isolation capability, safe and reliable;
③ Soft line output, easy to use and flexible.
2.Ambient Conditions:
① Ambient temperature: -55℃~+85℃;
② Relative humidity: ≤90% at 40℃;
③ Atmospheric pressure: 860~1060mbar(about 650~800mmHg).
3.Operating Frequency Range: 20Hz~1kHz
4.Insulation Thermal Class:Class B (130°C)
5.Safety Features:
① Insulation resistance: >1000MΩ in normal condition;
②Insulation withstand voltages: 6KV 50Hz/1min;
③ Fire retardancy: In conformity with UL94-V0.
6. Outline Drawing, Installation Dimension and Coil Diagram:( tolerance ± 1mm )
① Outline drawing and installation dimensions are shown in Figure 1 :
② The coil diagram is shown in Figure 2 :

7. Typical application and performance parameters:
See the table below for the application performance parameters shown in Figure 3.
 
Model  | Rated Input Current  | Rated Output Current  | Rated Sampling Resistance  | Rated Sampling Voltage  | Phase Shift  | Non-linearity  | Linear Range  | 
TA8595-01M  | 1A  | 1mA  | 100Ω  | 0.1V  | ≤60'  | ≤0.5%  | ≥2 times of the rated value  | 
TA8595-02M  | 1A  | 0.5mA  | 400Ω  | 0.2V  | ≤60'  | ≤0.5%  | 
● Notes:
a. In practical applications, the sampling resistance should be less than or equal to the rated value given in the above table, which will improve the nonlinearity and phase shift;
b. If the conversion ratio required by the user is different from the above, it can be customized according to the user's requirements.
8. Attention:
① The primary of the current transformer should be connected in series with the circuit being measured, and the secondary should work close to a short circuit condition.
② The secondary circuit of the current transformer should not be open-circuited. Therefore, please do not install fuses.